The LT-X15 is a Type 1 SPD rated 15kA Iimp (10/350 µs) for the main panel at the LPZ0 to LPZ1 boundary. It uses a graphite spark gap rather than a varistor, so it carries no follow current and no standing leakage — the property that matters where the device sits upstream of an RCD. It is the entry-level Type 1 rating for buildings with an external lightning protection system and a calculated partial lightning current below 15kA per pole.
Type 1 SPD with Graphite Spark Gap: Key Features
Tested With the Lightning Waveform
A Type 1 device is defined by its test, not by its marketing: 10/350 microseconds is a partial lightning current waveform with a long tail that carries a great deal of charge. Fifteen kiloamps of that waveform is the entry-level rating for a structure with an external lightning protection system.
Graphite Gaps Instead of Varistors
The switching element is a graphite spark gap, which behaves differently from a metal oxide varistor: it does not conduct at normal voltage, so there is no standing leakage and no ageing from continuous energisation. It fires when the voltage rises, then extinguishes.
No Follow Current to Clear
Because the gap extinguishes at the natural current zero, there is nothing for the installation’s protective device to interrupt after the surge passes. That is the property that lets a Type 1 device be installed at the main panel without a large upstream fuse purely for the SPD.
Position in the Protection Zone
This device belongs at the boundary between LPZ0 and LPZ1, the point where a lightning current can still appear on the conductors. Downstream of it, the environment is calmer and a Type 2 or Type 3 device handles the residual.
Specifications
| Series | LT-X15 Type 1 voltage switching SPD |
|---|---|
| IEC classification | Type 1 / Class I, tested to IEC 61643-11 |
| Maximum continuous voltage Uc | 275 / 320 / 385 / 440 VAC |
| Impulse discharge current Iimp | 15 kA (10/350 µs) |
| Voltage protection level Up | ≤2.5 kV |
| Protective element | graphite spark gap (GDT) |
| Follow current | none — self-extinguishing at current zero |
| Configurations | 1P, 2P, 3P, 4P |
| Mounting | 35mm DIN rail to EN 60715, main panel |
| Application interface | LPZ0 to LPZ1, service entrance with LPS |
| Related models | LT-X30 (30kA), LT-X50 (50kA), LT-T25 (25kA with MOV hybrid) |
Reading the LT-X15 specification
Iimp is the figure that separates a Type 1 device from everything else on the rail, and it is expressed per pole. The 15kA rating is tested with a 10/350 µs waveform because that approximates the current of a direct strike rather than the induced surge a Type 2 device sees; the long tail carries far more charge than an 8/20 impulse of the same peak.
Whether 15kA is sufficient comes from the lightning risk assessment, not from the size of the building. A structure with a defined LPS, a single set of down conductors and a supply that arrives underground usually lands below this figure. Where the assessment returns a higher partial lightning current, the rating steps up to the LT-X30 or LT-X50 in the same housing, so the panel layout does not change.
Wiring Diagram & Connection
The LT-X15 is a graphite spark gap, so it is wired like a switch rather than a varistor bank: in parallel across the conductors at the building entry, with the earth path kept as straight and as short as the enclosure allows.

LT-X15 — The Device Behind a Lightning Protection System
Once a building has an external lightning protection system, the phrase ‘surge protection’ means something more specific than it does in an ordinary installation. Part of the lightning current can now enter the electrical installation through the equipotential bonding, and the device at the entry has to survive a waveform with a long charge tail rather than the short induced spike that a Type 2 device is built for.
The fifteen kiloamp rating corresponds to the lower end of that exposure: a building with a defined lightning protection system, a single set of down conductors and a supply that arrives underground or through a well-shielded route. Where the structure is taller, the down conductors more numerous or the supply overhead and exposed, the thirty and fifty kiloamp versions of the same device are the correct choice.

Factory-Direct OEM / ODM Manufacturer
We Manufacture, You Brand
Module moulding in house · MOV selection and thermal parts · OEM branding
Every LT component on this page — housing, busbar, varistor stack and thermal disconnector — is produced and assembled at our own plant in Liushi, Zhejiang, which is why a special voltage, pole count or marking requirement costs you a production slot rather than a new supplier qualification. The full AC range sits on our Type 1 SPD range page.
- OEM branding — logo, model number and rating text printed on the module front and the carton.
- ODM options — housing colour, pole count, voltage window, remote-signal contact and retail packing.
- Testing — residual voltage and thermal trip checked on every unit, records kept per batch.
- MOQ — quoted per configuration — mixed models can share one container.

Buying Guide
Type 1 selection follows the lightning risk assessment rather than the size of the building, so start from the assessment and work back to the device.
- Confirm that the building has an external lightning protection system and note the lightning protection level from the risk assessment.
- Check how the supply enters — underground, overhead, or with a shielded cable — because that sets the share of lightning current reaching the conductors.
- Read the required Iimp from the assessment or the local standard, and choose 15, 30 or 50kA accordingly.
- Select the pole arrangement to match the earthing system, remembering that a N-PE gap is normally needed in TT installations.
- Plan the Type 2 stage downstream; a Type 1 device alone does not bring the let-through voltage to a level suitable for electronics.
Where the LT-X15 is the wrong choice
A building without an external lightning protection system does not need a Type 1 device at all — a Type 2 SPD such as the LT-40 is the correct entry device there, and adding a gap device only raises the clamping level. Where the risk assessment returns a partial lightning current above 15kA per pole, the LT-X30 or LT-X50 must be used instead; the housing is the same, so the drawing changes by a line item only. The LT-X15 is also not a replacement for downstream Type 2 or Type 3 protection, because its clamping level is deliberately high.

How We Support Your Business

OEM / ODM
We print your brand on the module front and pack to your carton design; ODM covers new pole layouts, alternative voltage windows and signalling options.
Tooling in house · Branded packing · ODM design

Wholesale
Volume pricing on the whole LT range, with sample lots for tender packages and full containers for stock orders.
Bulk pricing · Samples · Firm lead times

Distributor Support
Technical files, selection curves and local standard guidance so your sales team can specify the right type on the first visit.
Datasheets · Selection help · Training
Ready to Order the LT-X15?
Send us the lightning risk assessment result and the supply arrangement and we will confirm whether the LT-X15 or a higher Iimp rating applies, with the downstream Type 2 stage matched to it.
Frequently Asked Questions
What is a Type 1 SPD used for?
A Type 1 SPD is installed at the service entrance where an external lightning protection system exists, and is rated to discharge part of a direct strike current. It sits at the LPZ0 to LPZ1 boundary and is followed by a Type 2 stage downstream — it cannot be the only protective device in the installation.
What does 15kA Iimp at 10/350 µs mean?
It is the peak of a simulated partial lightning current with a 10 microsecond rise and a 350 microsecond decay. The long tail carries far more charge than an 8/20 impulse, which is why a Type 1 device cannot simply be a Type 2 device with a bigger label. The figure is per pole.
Does a Type 1 SPD need a backup fuse?
Not for follow current — a graphite gap extinguishes at the natural current zero, so there is no sustained fault for a fuse to clear. The upstream device is chosen for the installation’s fault level. Where local rules require a disconnector, an LT-SSD unit can be added.
Is a spark gap better than a varistor?
Neither is better in absolute terms. A gap has no leakage and no follow current, so it suits the entry point where a lightning current may arrive. A varistor clamps more precisely, which is why the two technologies are used together in a staged design.
Which pole version suits a three-phase TT system?
A three-pole plus neutral arrangement, with the gap between neutral and earth placed at the entry. In TT systems the neutral-to-earth path is a separate concern from the phase paths.
How long does the device last?
A gap element does not age from continuous voltage the way a varistor does, so its life is governed by the number and magnitude of operations. After a significant event, inspection of the indicator and a check of the protection level is the appropriate routine.