Low Up Surge Arrester 0.8kV — LT-40GX

LT-40GX — Ultra-Low Residual Voltage Type 2 SPD

A 40kA Type 2 device specified for its clamping voltage rather than its current: 0.8kV on the 275V code, rising to 1.2kV at 440V. For boards where the equipment downstream has a low impulse withstand and a conventional protector would leave too little margin.

Model

✓

LT-40GX SPD product photo

LT-40GX Ultra-Low Up Type 2 Surge ProtectorType 2 (T2) · In 20kA / Imax 40kA · Up 0.8–1.2kV

Request a Wholesale Quotation

Type 2 (Class II) · Up 0.8kV · MOQ quoted per configuration

Up 0.8kV
In 20kA
Imax 40kA
Product Details
  • IEC class — Type 2 (T2) SPD to IEC 61643-11
  • Uc — 275 / 320 / 385 / 440 VAC
  • In / Imax — 20 kA / 40 kA at 8/20 µs
  • Up — 0.8 / 1.0 / 1.0 / 1.2 kV by voltage code
  • Poles — 1P, 2P, 3P, 4P
  • Advantage — lowest Up in the 40kA class
  • Application — sensitive electronics, cascaded second stage
Categories: ,

The LT-40GX is a low-Up surge arrester reaching 0.8kV on the 275V code, against 1.4kV for the standard LT-40. Same 20/40kA rating, same 18mm body, but the element is selected for clamping rather than capacity. It is specified where the margin between the residual voltage and the equipment withstand has run out.

Low Up Surge Arrester 0.8kV for Sensitive Loads

Clamping Voltage Is the Number That Reaches the Load

Discharge current tells you what the device survives; protection level tells you what the equipment experiences. The GX version takes the 40kA platform and re-optimises the element for a lower let-through, reaching 0.8kV on a 275V supply where a standard device of the same rating sits around 1.4kV.

Where the Margin Has Run Out

Modern electronic equipment often has an impulse withstand of 1.5kV or 2.5kV at its terminals. Once cable length, protection level and a safety margin are added up, a conventional device at 1.5kV or higher can leave nothing in reserve. This is the device that restores the margin without changing the panel layout.

Works as a Second Stage

In a cascaded design the first device absorbs the energy and the second defines the let-through. Because the GX clamps low while still handling 40kA, it can serve as that second stage without the co-ordination gap becoming critical, which simplifies the geometry of a retrofit.

Four Voltage Codes, Four Levels

The protection level rises with the continuous voltage window, from 0.8kV at 275V to 1.2kV at 440V. Choosing the lowest code the system allows is therefore a direct way to gain clamping margin, and it is the first decision in specifying this device.

Specifications

Series LT-40GX ultra-low residual voltage Type 2 SPD
IEC classification Type 2 / Class II, tested to IEC 61643-11
Maximum continuous voltage Uc 275 / 320 / 385 / 440 VAC
Nominal discharge current In 20 kA (8/20 µs)
Maximum discharge current Imax 40 kA (8/20 µs)
Voltage protection level Up 0.8 kV (275V), 1.0 kV (320V and 385V), 1.2 kV (440V)
Configurations 1P, 2P, 3P, 4P
Module width 18mm per pole
Positioning second stage, close to sensitive loads
Related models LT-40 standard (1.4kV and above), LT-10C (Type 3 equipment stage)

Reading the LT-40GX specification

Up is the number that reaches the load, and it is the one figure a standard 40kA device cannot push much lower without changing technology. The GX version reaches 0.8kV at 275V, 1.0kV at 320V and 385V, and 1.2kV at 440V — roughly a 40% reduction against the standard body.

That reduction is bought with a different element selection, not with a larger rating. In and Imax stay at 20kA and 40kA, which is why the device fits the same rail position as the standard unit and can be substituted at drawing stage.

Wiring Diagram & Connection

The LT-40GX is wired like any 40 kA Type 2 unit but is placed where residual voltage matters: directly upstream of the drive, meter or control supply it is protecting, with the earth return kept on the same bar as that equipment.

LT-40GX 0.8kV residual voltage SPD wiring diagram for sensitive loads
LT-40GX connection scheme ahead of sensitive electronic equipment.

LT-40GX — Specified by Its Protection Level, Not Its Current

Surge protector catalogues lead with discharge current because it is easy to compare, but the figure that decides whether equipment survives is the residual voltage at the terminals. Two devices can both be rated 40kA and differ by nearly a kilovolt in what they let through, and that difference is usually worth more than the current rating in a modern installation.

The trade is real: a lower clamping voltage means a varistor working nearer its threshold, so the device is selected where the exposure justifies it rather than as a blanket upgrade. In practice that means boards feeding controls, drives, communications equipment and medical or laboratory loads, where the equipment withstand is known and the margin is being calculated rather than assumed.

LT-40GX ultra low residual voltage Type 2 surge protector four-pole on DIN rail

Factory-Direct OEM / ODM Manufacturer

From Mould to Carton, Under One Roof

Liushi, Zhejiang · fully automatic SPD line · OEM, ODM and wholesale

Choices that normally need a tooling investment — a different housing colour, an extra pole, a longer terminal shroud — are routine here because the machine shop, the moulding area and the assembly line are on the same site. That is the practical difference between buying from the plant and buying from a catalogue. See Type 2 SPD range for the models this platform covers.

  • In-house moulds — new cavities cut and proven without an outside toolmaker.
  • Assembly — semi-automatic cells keep torque and fit consistent across a batch.
  • Quality gate — incoming varistors are graded before they reach the assembly line.
  • Export packing — cartons, labels and pallet marks prepared to the destination market.

LT-40GX low-Up SPD — automatic SPD production line running at LEITAI

Buying Guide

Specify this device from the equipment withstand downwards. The current rating is secondary to the clamping figure.

  1. Establish the impulse withstand voltage of the equipment being protected, from its datasheet or the applicable product standard.
  2. Choose the lowest voltage code the system permits, since the protection level rises with Uc.
  3. Subtract the let-through from the equipment withstand and check the remaining margin, allowing for cable length between the SPD and the load.
  4. Confirm the co-ordination with any upstream device, particularly the cable length between stages.
  5. Verify the backup protection rating for the board fault level as with any 40kA SPD.

Where the LT-40GX is the wrong choice

It is not a Type 3 device and does not replace terminal protection where the equipment is genuinely sensitive — the LT-10C covers that position. Nor should it be used as the first stage at a main board where the energy is high; the lower clamping comes with less margin for repeated large surges.

LT-40GX low-Up SPD — manual module assembly zone at the Lei tai factory

How We Support Your Business

LT-40GX low-Up SPD — component feeding and assembly equipment at LEITAI

OEM / ODM

Learn more →

Private-label programmes run on the same type-tested platform, so a rebranded unit keeps the ratings, curves and approvals of the original.


Type-tested base · Rebranding · Carton design

LT-40GX low-Up SPD — production hall feeding the SPD assembly lines

Wholesale

Learn more →

Container planning, mixed pallets and consistent batch quality for wholesalers supplying panel builders and contractors.


Container plan · Mixed pallets · Batch records

LT-40GX low-Up SPD — certificate and honours wall at the LEITAI factory

Distributor Support

Learn more →

Priority production slots and a named account contact for partners promoting the range at trade shows and in tender work.


Priority slots · Named contact · Tender files

Ready to Order the LT-40GX?

Tell us the withstand voltage of the equipment and the system voltage, and we will confirm which LT-40GX code gives you the margin you need, with the upstream stage matched to it.

Contact Our Sales Team

Frequently Asked Questions

What does low Up mean on an SPD?

Up is the residual voltage the protected equipment sees during a surge. A lower figure leaves more margin between that voltage and the equipment’s withstand rating.

How much lower is 0.8kV than 1.4kV?

About 40% lower at the 275V code. That difference is often what decides whether a sensitive load survives a surge at the edge of its rating.

Does low Up reduce the surge capacity?

Not the In and Imax ratings, which stay at 20kA and 40kA. The element is selected differently, but the device is not a smaller one.

Can it be the only device in the installation?

It can, but it is usually specified as the second stage behind a higher-energy device. Used alone at the origin it works, though the co-ordination benefit of cascading is lost.

Is it worth the premium in an ordinary building?

Usually not. Where the equipment has a generous withstand and the exposure is modest, a standard 40kA device is the economical choice. The GX earns its place where the margin is being calculated against a specific withstand value.

Does the low clamping level affect service life?

The element operates closer to its threshold, so the device is chosen for installations with measured exposure rather than for highly exposed sites. Where both low clamping and high exposure apply, a cascaded arrangement is the correct answer.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “Low Up Surge Arrester 0.8kV — LT-40GX”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts