Type 2 Surge Protector 80kA for Risers — LT-80

LT-80 — OEM & Distributor Surge Protector Supplier

A 40kA nominal, 80kA maximum Type 2 device for riser panels and sub-main boards that sit between the building intake and the floor distribution, in the same 18mm-per-pole body as the LT-60 so the panel layout does not change when the rating steps up.

Model

✓

LT-80 SPD product photo

LT-80 High Capacity Type 2 Surge ProtectorType 2 (T2) · In 40kA · Imax 80kA · Up ≤2.5kV

Request a Wholesale Quotation

Type 2 (Class II) · In 40kA · MOQ quoted per configuration

In 40kA
Imax 80kA
Same width as LT-60
Product Details
  • IEC class — Type 2 (T2) SPD to IEC 61643-11
  • Uc — 385 / 440 VAC
  • In / Imax — 40 kA / 80 kA at 8/20 µs
  • Up — ≤2.5 kV
  • Poles — 2P, 4P standard
  • Width — same body as LT-60, 18mm per pole
  • Application — riser panels, sub-main boards, plant rooms
Categories: ,

The LT-80 is an 80kA Type 2 surge protector for riser and sub-main panels, rated In 40kA and Imax 80kA. It is one width step above the LT-60 with the same clamping level, and it is specified where a vertical riser serves several floors and the protection point sits partway up the building.

Type 2 Surge Protector 80kA for Riser Panels

A Riser Panel Is Not a Final Board

Vertical distribution in a multi-storey building concentrates many downstream circuits behind one panel, and the cable run from the intake is long enough to pick up induced transients along the way. Forty kiloamps nominal gives that panel a discharge path proportionate to what it actually collects.

One Width Step, Everything Else Unchanged

The LT-80 is built in the same body as the LT-60, so a specification that moves from 60kA to 80kA does not change the cut-out, the comb length or the distance to the earth bar. For a consultant issuing a generic drawing across several buildings, that is the property that keeps the detail drawing reusable.

Cooler Operation at Continuous Load

The larger stack runs at a lower current density for the same leakage, which is why these devices are often chosen in plant rooms where ambient temperature is already elevated. The electrical benefit is a longer service interval rather than a lower clamping voltage.

Paired With a Low-Up Device Downstream

At 2.5kV this unit is the energy absorber, not the last word in clamping. In a riser application it is normally followed at floor level by a 20kA or 40kA device with a lower protection level, and the two are selected together rather than separately.

Specifications

Series LT-80 heavy duty AC surge protective device
IEC classification Type 2 / Class II, tested to IEC 61643-11
Maximum continuous voltage Uc 385 / 440 VAC
Nominal discharge current In 40 kA (8/20 µs)
Maximum discharge current Imax 80 kA (8/20 µs)
Voltage protection level Up ≤2.5 kV
Configurations 2P and 4P standard, other layouts on request
Module width 18mm per pole, identical body to LT-60
Mounting 35mm DIN rail to EN 60715
Status indicator per pole, thermal disconnector
Positioning sub-main and riser level, upstream of floor boards
Related models LT-60 (30/60kA), LT-100 and LT-160 (wider body), LT-80RT plug-in version

Reading the LT-80 specification

A riser panel is not a final board. The cable run from the main intake is long enough to add inductance, and the panels above it see a surge that has already been partly attenuated but is still above what a final-circuit device should take. The 80kA rating covers that middle position, and the 40kA In figure is what allows it to operate repeatedly without drifting.

Width grows by one step over the LT-60 but the terminal arrangement and the 2.5kV clamping level stay the same, so a riser design can be standardised across both ratings without changing the enclosure.

Wiring Diagram & Connection

The LT-80 shares the LT-60 housing, so a panel already drilled for LT-60 drops the 80 kA unit into the same footprint. The only adjustment is the feeder tail: it has to carry the higher Imax without adding loop length.

LT-80 80kA arrester wiring diagram for sub-main distribution panels
LT-80 connection detail, 4P unit with L1 / L2 / L3 / N and PE paths.

LT-80 — Sizing a Riser Without Oversizing the Building

A riser panel collects the transients of every floor it serves, which is why the same 40kA device that looks generous in a small plant room looks marginal at the bottom of a twelve-storey riser. The 80kA maximum figure exists for that accumulation, and it comes without the width penalty that the 100kA class carries.

The choice between LT-80 and the wider LT-100 is usually made on fault level and on how much of the building sits downstream, not on the surge current alone. Where the incoming feeder is long, the transformer is close by, or the panel also feeds lift and pump loads, the next step up is justified. Where the riser serves ordinary lighting and socket circuits, this rating is the economical and technically sound stopping point.

LT-80 Type 2 surge protector four-pole 275VAC for sub-main panels

Factory-Direct OEM / ODM Manufacturer

We Manufacture, You Brand

Module moulding in house · MOV selection and thermal parts · OEM branding

Every LT component on this page — housing, busbar, varistor stack and thermal disconnector — is produced and assembled at our own plant in Liushi, Zhejiang, which is why a special voltage, pole count or marking requirement costs you a production slot rather than a new supplier qualification. The full AC range sits on our Type 2 SPD range page.

  • OEM branding — logo, model number and rating text printed on the module front and the carton.
  • ODM options — housing colour, pole count, voltage window, remote-signal contact and retail packing.
  • Testing — residual voltage and thermal trip checked on every unit, records kept per batch.
  • MOQ — quoted per configuration — mixed models can share one container.

LT-80 Type 2 SPD — automatic soldering station in the SPD workshop

Buying Guide

Four questions decide whether this rating is right for a riser panel or whether the design should step up to the wide-body class.

  1. Count the downstream boards the panel serves and note their individual protection ratings.
  2. Check the fault level at the panel; high fault currents push the backup protection choice, not the SPD rating.
  3. Confirm the pole arrangement matches the earthing system, particularly whether a neutral conductor is distributed.
  4. Decide the second stage at floor level and check the cable length between the two devices supports co-ordination.
  5. Confirm the enclosure depth suits the SPD plus its backup device before the panel is fabricated.

Where the LT-80 is the wrong choice

It is not a main-board device: at the intake, the fault level and the energy normally call for the LT-100 or LT-160. It is also not a substitute for final-board protection — a floor board still needs its own Type 2 or Type 3 device.

LT-80 Type 2 SPD — automated soldering cells at the LEITAI factory

How We Support Your Business

LT-80 Type 2 SPD — automatic assembly equipment building SPD modules

OEM / ODM

Learn more →

We print your brand on the module front and pack to your carton design; ODM covers new pole layouts, alternative voltage windows and signalling options.


Tooling in house · Branded packing · ODM design

LT-80 Type 2 SPD — workshop floor and material totes at the LEITAI plant

Wholesale

Learn more →

Volume pricing on the whole LT range, with sample lots for tender packages and full containers for stock orders.


Bulk pricing · Samples · Firm lead times

LT-80 Type 2 SPD — type test certificates and honours on show at LEITAI

Distributor Support

Learn more →

Technical files, selection curves and local standard guidance so your sales team can specify the right type on the first visit.


Datasheets · Selection help · Training

Ready to Order the LT-80?

Share the riser diagram and the fault level at the panel, and we will confirm whether the LT-80 or the wide-body LT-100 is the better fit, with the backup protection sized for your board.

Contact Our Sales Team

Frequently Asked Questions

What is a riser panel SPD?

It protects the distribution point on a vertical riser serving several floors, where the surge has been partly attenuated by cable length but is still above final-circuit levels.

80kA Imax or 40kA In, which matters?

Both, for different reasons. In 40kA is the repeated-duty rating that specifications use; Imax 80kA is the single-shot limit.

Can it replace a main-board device?

No. At the intake the energy and fault level are higher, and the 100kA or 160kA units are the correct ratings.

What happens at end of life?

The thermal disconnector opens and the status indicator on the affected pole changes. The device is then replaced as a module; it does not reset and must not be left in service with an open indicator.

Which backup device do you recommend?

A fuse or breaker rated to the SPD’s stated maximum backup protection for the prospective fault current at the panel, or a dedicated SPD disconnector from the LT-SSD range. We state the recommendation on the quotation for the specific board.

Is a plug-in version available at this rating?

Yes — the LT-80RT uses plug-in cartridges on a common base, which is preferred where maintenance staff replace cartridges without isolating the panel.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “Type 2 Surge Protector 80kA for Risers — LT-80”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts