Double Terminal 40kA SPD — LT-40N

LT-40N — Narrow Body SPD with Upper and Lower Terminals

A 40kA Type 2 device whose terminals are split across two levels: incoming conductors land on the upper deck and outgoing on the lower, with different cross-sections accepted on each. Built for boards where the busbar route and the cable route cannot share one terminal level.

Model

✓

LT-40N SPD product photo

LT-40N Double-Deck Type 2 Surge ProtectorType 2 (T2) · In 20kA / Imax 40kA · Double-deck terminals

Request a Wholesale Quotation

Type 2 (Class II) · Double-deck terminals · MOQ quoted per configuration

Double-deck terminals
In 20kA
Imax 40kA
Product Details
  • IEC class — Type 2 (T2) SPD to IEC 61643-11
  • Uc — 275 / 320 / 385 VAC
  • In / Imax — 20 kA / 40 kA at 8/20 µs
  • Up — 1.5 / 1.5 / 1.8 kV by voltage code
  • Terminals — upper 12mm, lower 15mm, separate decks
  • Poles — 1P+NPE, 2P, 3P+NPE, 4P
  • Application — narrow cabinets, retofit boards
Categories: ,

The LT-40N is a 40kA Type 2 SPD with two terminal levels, built for cabinets where the incoming and outgoing conductors cannot share a single terminal block. Electrical ratings match the standard 40kA range — In 20kA, Imax 40kA — but the double-deck arrangement accepts different cross-sections at each level.

Double Terminal 40kA SPD for Compact Cabinets

Two Terminal Levels, One Device

In a board where the incoming supply arrives on a heavy busbar and the outgoing circuit uses cable, both connections normally converge on the same terminal, which is awkward to torque and hard to inspect. Splitting the terminals across an upper and a lower deck keeps them separate and lets each take the conductor size it actually sees.

Different Cross-Sections by Design

The upper deck accepts 12mm conductors and the lower deck 15mm, reflecting the typical difference between the incoming feed and the earth return. Providing the right capacity at each point is what keeps the connection resistance low where it matters most.

Narrow Enough for Retrofit

Boards built twenty years ago were not laid out with surge protection in mind, and the free space is often a shallow strip beside the incomer. A device whose terminals are stacked rather than spread along the rail fits that strip where a conventional module would foul the busbar.

Consistent With the 40kA Family

Discharge ratings and protection levels match the standard LT-40, so specifying the double-deck version for installation reasons does not change the electrical design or the backup protection calculation.

Specifications

Series LT-40N double-deck Type 2 SPD
IEC classification Type 2 / Class II, tested to IEC 61643-11
Maximum continuous voltage Uc 275 / 320 / 385 VAC
Nominal discharge current In 20 kA (8/20 µs)
Maximum discharge current Imax 40 kA (8/20 µs)
Voltage protection level Up 1.5 kV (275V and 320V), 1.8 kV (385V)
Terminals upper deck 12mm, lower deck 15mm
Configurations 1P+NPE, 2P, 3P+NPE, 4P (with signal contact option)
Mounting 35mm DIN rail to EN 60715
Application narrow cabinets, retrofit installations
Related models LT-40 (single-level terminals), LT-40GX (low Up), LT-40 slim (monitored)

Reading the LT-40N specification

The second terminal level exists because of a wiring problem, not an electrical one. In a retrofit cabinet the incoming feeder and the outgoing circuit conductors often arrive at different sizes, and a single-level SPD forces both into one clamp or a separate terminal block. Two levels keep the connection point inside the device.

Up is 1.5kV on the 275V and 320V codes and 1.8kV on 385V. The Uc range stops at 385V, so a 440V system is outside this model’s specification and the standard LT-40 should be used instead.

Wiring Diagram & Connection

The LT-40N uses two terminal levels, one above the other, so the incoming tail lands on the top level and the outgoing conductor on the bottom. That is what allows a 40 kA unit to be wired in a cabinet with almost no horizontal space.

LT-40N double deck terminal SPD wiring diagram for narrow panels
LT-40N two-level terminal layout, top and bottom entry.

LT-40N — A Terminal Arrangement for Real Panels

Most SPD failures in the field are not failures of the varistor. They are installation problems: a terminal that could not be torqued properly because two conductors of different sizes were forced into it, or an earth lead run too long because the device would not fit where the earth bar was. The double-deck terminal addresses the first of those directly.

It is a modest looking change with a real effect on the finished board. Incoming and outgoing conductors are visually separated, the torque check is straightforward, and the inspector can see which conductor goes where without reading a drawing. For a contractor doing repeat retrofit work, that saves time on every board rather than on one project.

LT-40N Type 2 surge protector with double deck terminals four-pole on DIN rail

Factory-Direct OEM / ODM Manufacturer

Tooling We Own, Standards We Follow

IEC 61643-11 platform · 250kA test station · OEM and ODM programmes

The modules on this page share a platform that has already passed type testing, so a variant order inherits that evidence instead of starting again. Manufacturing sits beside the laboratory, which is how we can verify a change before it enters a customer’s catalogue. Browse the rest of the range on Type 2 SPD range.

  • Design control — drawings, BOM and test limits held under one quality system.
  • Lab access — impulse and residual-voltage checks run before a variant is released.
  • Branding — plate printing, laser marking and carton artwork prepared from your files.
  • Order size — sample lots, LCL and full containers all quoted from the same line.

LT-40N Type 2 SPD — automated production line at the LEITAI factory

Buying Guide

Specify this version from the panel layout rather than from the electrical schedule, since its advantage is physical.

  1. Confirm the conductor sizes arriving on the upper and lower decks match the 12mm and 15mm capacity.
  2. Check the free rail strip and the busbar route; the stacked terminals need vertical clearance above the device.
  3. Confirm the voltage code and the resulting protection level, which differs between the 275/320 and 385 versions.
  4. Decide whether a signal contact is needed on the 4P version, since that changes the ordering code.
  5. Confirm the backup protection rating against the board fault level, as with any 40kA device.

Where the LT-40N is the wrong choice

Where the cabinet has space for a normal terminal arrangement, this device adds cost without benefit — the LT-40 covers the same electrical duty. The 385V limit also rules it out of 480V networks.

LT-40N Type 2 SPD — operators assembling SPD modules on the LEITAI line

How We Support Your Business

LT-40N Type 2 SPD — dual soldering machines on the LEITAI production line

OEM / ODM

Learn more →

Housing colour, pole count, voltage window, alarm contact and retail packaging built on our standard SPD platform — your logo on the front, your reference on the side.


Custom marking · Private label · Own artwork

LT-40N Type 2 SPD — selective soldering of surge protector boards at LEITAI

Wholesale

Learn more →

Factory-direct pricing with a per-item MOQ, mixing SPD models and backup protectors in one container for importers, panel builders and catalogue sellers.


Factory pricing · Mixed models · Container loading

LT-40N Type 2 SPD — electrical test bench used for SPD verification

Distributor Support

Learn more →

Account management, local voltage and standard advice, plus priority production slots for partners building an SPD range in their market.


Account manager · Market advice · Priority slots

Ready to Order the LT-40N?

Send a photograph or drawing of the board layout and we will confirm whether the double-deck terminal arrangement solves the installation, together with the right pole configuration.

Contact Our Sales Team

Frequently Asked Questions

What is a double-deck terminal SPD?

It has two separate terminal levels in one device, so incoming and outgoing conductors of different cross-sections can be terminated without an additional block.

Does it have the same rating as the LT-40?

Yes: In 20kA and Imax 40kA. The difference is the terminal arrangement and the Uc range, which stops at 385V.

Can it be used on a 480V system?

No. The maximum Uc code is 385V; a 480V network needs the 440V code available on the standard LT-40.

Does the 385V version have a different protection level?

Yes, 1.8kV rather than 1.5kV for the 275V and 320V codes. That figure should be checked against the withstand of the equipment downstream.

Is a remote signal available?

On the four-pole version a signal contact can be specified. Confirm the requirement at ordering stage because it changes the model reference.

How is the earth connection made?

Through one of the terminal decks by the shortest practical route to the earth bar. The stacked layout usually makes that route shorter than with a single-level device.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “Double Terminal 40kA SPD — LT-40N”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts