DIN Rail Surge Protector 18mm — LT-40 Slim

LT-40 Slim — Monitored SPD for Critical Panels

The thin version of the 40kA Type 2 platform: an 18mm single-pole module with a 1200V temporary overvoltage withstand, a 25kA short-circuit withstand and a remote signalling contact fitted as standard. For distribution boards that are monitored rather than inspected.

Model

✓

LT-40 Slim (YX) SPD product photo

LT-40 Slim Monitored Type 2 Surge ProtectorType 2 (T2) · 18mm slim · TOV 1200V · Remote signal standard

Request a Wholesale Quotation

Type 2 (Class II) · 18mm slim · MOQ quoted per configuration

18mm slim
TOV 1200V
Signal standard
Product Details
  • IEC class — Type 2 (T2) SPD to IEC 61643-11
  • Uc — 275 / 320 / 385 / 440 VAC
  • In / Imax — 20 kA / 40 kA at 8/20 µs
  • Up — 1.2 / 1.5 / 1.8 / 2.0 kV (L-N) by code
  • TOV withstand — 1200V temporary overvoltage
  • Short-circuit withstand — 25 kA
  • Remote contact — fitted as standard on every module
Category:

The LT-40 Slim is an 18mm DIN rail surge protector with the same 20/40kA rating as the standard LT-40, plus a 25kA short-circuit withstand and a 1200V temporary overvoltage window. It is specified where the enclosure depth or the rail length leaves no room for a full-width module, and the remote signalling contact reports a failed cartridge without opening the panel.

DIN Rail Surge Protector 18mm with Remote Signalling

Eighteen Millimetres, Fully Featured

A monitoring contact normally adds width, because the auxiliary block clips onto the side of the device. Here it is built into the same 18mm body, which means a board can be fully monitored without losing a single extra rail position — the property that makes this version viable in retrofit work.

A 1200V Temporary Overvoltage Window

A temporary overvoltage is not a surge: it lasts seconds or minutes and comes from a lost neutral, a faulty transformer tap or a generator transfer. A device that cannot ride through it will fail and take the board down. The 1200V withstand is what lets this unit stay in service through that condition.

Short-Circuit Withstand of 25kA

End-of-life failure of a varistor is a short circuit, and the board has to survive it until the backup device clears. A 25kA withstand means the module does not rupture on the fault levels found in most commercial boards, which matters more than the discharge rating in that scenario.

Terminals That Take Real Cable

The terminal range covers 6 to 25mm², which is the practical size for the short, thick leads that a low-inductance SPD connection needs. Narrow terminals force installers onto thinner cable and quietly raise the effective protection level.

Specifications

Series LT-40 slim monitored Type 2 SPD
IEC classification Type 2 / Class II, tested to IEC 61643-11
Maximum continuous voltage Uc 275 / 320 / 385 / 440 VAC
Nominal discharge current In 20 kA (8/20 µs)
Maximum discharge current Imax 40 kA (8/20 µs)
Voltage protection level Up 1.2 kV (275V code) to 2.0 kV (440V code), L-N
Temporary overvoltage TOV 1200V withstand
Short-circuit withstand 25 kA
Terminal capacity 6 to 25mm²
Module width 18mm for 1P, 36mm for 1P+NPE
Remote signalling volt-free contact, standard on all versions
Related models LT-40 standard (fixed module), LT-40GX (lowest Up), LT-10C (equipment stage)

Reading the LT-40 Slim specification

The width is the specification here. At 18mm the device occupies one module per pole, which is what allows a four-pole bank to fit a rail that would otherwise take three. The electrical ratings are unchanged from the standard body: In 20kA, Imax 40kA, and Up from 1.2kV on the 275V code to 2.0kV on 440V.

Two figures are worth reading separately. The 25kA short-circuit withstand sets the backup protection coordination, and the 1200V TOV window describes how long the device survives a temporary overvoltage from a fault on the network — both are installation-level figures rather than surge ratings.

Wiring Diagram & Connection

The slim LT-40 is an 18 mm single-pole module, so a single-phase board takes 18 mm and a 1+NPE arrangement takes 36 mm. Conductors from 6 to 25 mm² land directly in the terminal, which is what makes it usable on retrofit boards with no spare depth.

LT-40 slim 18mm monitored SPD wiring diagram with signal terminals
LT-40 slim-line connection: 1P 18 mm module, 1+NPE at 36 mm.

LT-40 Slim — Protection You Can See from the Control Room

In an unmonitored installation, a surge protector that has reached end of life looks exactly like one that is working. The window has changed colour, but nobody is standing in front of the board. The slim LT-40 answers that by making the signal part of the product rather than an accessory, so the panel reports its own condition through the same system that reports everything else.

The electrical differences matter too. The 1200V temporary overvoltage withstand and the 25kA short-circuit withstand are both about surviving abnormal conditions rather than discharging surges, and those conditions are exactly what takes boards down in practice. For a data centre, a hospital panel or any board on a maintenance contract, those figures justify the small premium over the fixed version.

LT-40 slim Type 2 surge protector 18mm module with remote signalling contact

Factory-Direct OEM / ODM Manufacturer

Your Specification, Our Production Line

Type-tested platform · private-label marking · batch test records

We quote from a real production schedule, not from a stock list, which is why a customer changing from a competitor’s module to ours usually keeps the same panel layout and only changes the label. Everything needed for that switch — drawings, curves and test sheets — is available before the order. The wider family is on Type 2 SPD range.

  • Pre-order pack — datasheet, dimension drawing and declaration for your technical file.
  • Branding — printed fronts, side references and instruction sheets in your language.
  • Consistency — same platform across the range keeps panel stock simple for your customers.
  • Support — a named contact for repeat orders and technical questions.

LT-40 slim Type 2 SPD — SPD assembly hall with automated lines at LEITAI

Buying Guide

This version is chosen when the board is monitored or when abnormal supply conditions are likely. Confirm both before ordering.

  1. Identify the monitoring system that will receive the contact and confirm whether it needs normally open or normally closed logic.
  2. Check the terminal capacity against the cable the installer will actually use for the SPD leads.
  3. Confirm the temporary overvoltage conditions the site may see, particularly where a generator or a long rural feeder is involved.
  4. Verify the backup protection rating against the board fault level, since the SPD withstand is only half of that calculation.
  5. Allow 18mm per pole and a route for the signal cable away from power conductors.

Where the LT-40 Slim is the wrong choice

It is not the lowest-Up option: where the load is sensitive, the LT-40GX reaches 0.8kV on the 275V code. Nor is it a serviceable-cartridge device in the same sense as the RT range; the slim body is fixed, so end-of-life replacement means changing the module.

LT-40 slim Type 2 SPD — module assembly zone with operators at LEITAI

How We Support Your Business

LT-40 slim Type 2 SPD — in-house assembly machinery for surge protectors

OEM / ODM

Learn more →

We print your brand on the module front and pack to your carton design; ODM covers new pole layouts, alternative voltage windows and signalling options.


Tooling in house · Branded packing · ODM design

LT-40 slim Type 2 SPD — automatic soldering station in the SPD workshop

Wholesale

Learn more →

Volume pricing on the whole LT range, with sample lots for tender packages and full containers for stock orders.


Bulk pricing · Samples · Firm lead times

LT-40 slim Type 2 SPD — calibration bench with instruments at LEITAI

Distributor Support

Learn more →

Technical files, selection curves and local standard guidance so your sales team can specify the right type on the first visit.


Datasheets · Selection help · Training

Ready to Order the LT-40 Slim (YX)?

If the board will be monitored, tell us the protocol and the contact logic and we will quote the LT-40 slim in the right pole configuration with the signal wiring detail for your panel drawings.

Contact Our Sales Team

Frequently Asked Questions

What does 18mm slim mean on an SPD?

It occupies a single 18mm module width per pole instead of the wider body used by standard 40kA devices, which matters where rail length is fixed.

What is the 1200V TOV figure?

It is the temporary overvoltage the device can withstand for a defined period, typically caused by a fault or a neutral displacement on the network. It is separate from the surge ratings.

How does remote signalling work?

A contact changes state when the cartridge fails, and it is wired back to the monitoring system. That allows a failed device to be identified without opening the enclosure.

Can I retrofit it into an existing board?

Yes, it uses the same 18mm footprint as the standard version, but the signal cable needs a route out of the enclosure. Plan that before the panel door is closed.

Does the slim body reduce the discharge rating?

No. The module is rated 20kA nominal and 40kA maximum, the same as the standard LT-40. The narrow body comes from a different internal arrangement, not from a smaller element.

Which protection level does the 385V code give?

The 385V code sits within the 1.2 to 2.0kV range and the exact figure is stated on the label and in the datasheet for that code. We confirm it with the quotation.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “DIN Rail Surge Protector 18mm — LT-40 Slim”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts