SPD Fuse 30kA Fuse-Free Disconnector — LT-SSD50X

LT-SSD50X — Fuse-Free Backup Protection for SPDs

A dedicated backup protector for surge protective devices, rated 30kA Iimp and 3A tripping current, in a four-pole body at 440V. It replaces the fuse or breaker normally used ahead of an SPD, removing the nuisance tripping that follows a surge and the risk of the wrong fuse being fitted during maintenance.

Model

✓

LT-SSD50X SPD product photo

LT-SSD50X SPD Backup ProtectorSPD disconnector · Iimp 30kA · It 3A · 440VAC

Request a Wholesale Quotation

SPD disconnector (accessory) · Iimp 30kA · MOQ quoted per configuration

Iimp 30kA
It 3A
No nuisance trip
Product Details
  • Function — dedicated backup protection for SPDs
  • Ue — 440 VAC
  • Iimp — 30 kA at 10/350 µs, without tripping
  • Tripping current It — 3 A
  • Poles — 1P, 2P, 3P, 4P
  • Application — TN-S, TN-C and TT systems
  • Standard — matched to IEC 61643-11 installations
Category:

The LT-SSD50X is a fuse-free disconnector for SPD back-up, rated 30kA Iimp with a 3A tripping threshold. It replaces the fuse that would otherwise sit in series with a Type 1 or Type 2 arrester, and it removes two problems at once: nuisance tripping after a surge, and the maintenance error of fitting the wrong fuse.

SPD Fuse 30kA Fuse-Free Disconnector

The Right Device Instead of a Guess

An SPD is normally protected by a fuse or breaker chosen by rule of thumb, and the rule is usually written for a different fault level from the one on site. A dedicated device removes the guess: it is selected against the SPD’s maximum backup rating rather than against a table.

No Nuisance Tripping After a Surge

A general-purpose MCB sees the surge current as an overcurrent and can trip, leaving the SPD disconnected and the installation apparently protected. This device passes 30kA of 10/350 without operating, which is the behaviour the SPD beside it needs.

3A Tripping Threshold

The 3A tripping current is chosen to clear a failed SPD element without being so sensitive that normal leakage or a modest surge opens it. That balance is what a general-purpose device cannot strike, because its curve was designed for cable protection.

Removes a Maintenance Error

When an SPD fuse blows, the replacement is often whatever is in the van. A dedicated device is labelled with its purpose, which makes an incorrect substitution much less likely and keeps the protection system valid after maintenance.

Specifications

Series LT-SSD SPD backup protection range
Function dedicated short-circuit and backup protection for SPDs
Rated voltage Ue 440 VAC
Impulse withstand Iimp 30 kA (10/350 µs) without tripping
Tripping current It 3 A
Configurations 1P, 2P, 3P, 4P
Earthing systems TN-S, TN-C, TT
Mounting 35mm DIN rail to EN 60715
Positioning immediately upstream of the SPD
Related models LT-SSD80 (80kA), LT-SSD160 (160kA)

Reading the LT-SSD50X specification

The tripping threshold is what makes it selective. At 3A it ignores the surge current that passes during a event and trips only on a sustained fault current, which is the condition a backup device exists to clear. A conventional fuse of the same rating cannot make that distinction and eventually operates on surge fatigue.

Iimp 30kA is the impulse withstand, which has to be at least as high as the arrester it protects. The device is available in 1P to 4P and is mounted in series ahead of the SPD on the same rail.

Wiring Diagram & Connection

The LT-SSD50X is not a surge protective device: it is wired in series in front of one, in place of the circuit breaker or fuse that would otherwise be used for back-up. The drawing shows the disconnector between the busbar and the SPD’s line terminal.

LT-SSD50X SPD back-up disconnector wiring diagram with arrester
LT-SSD50X connected in series ahead of the arrester it protects.

LT-SSD50X — What Belongs in Front of a 30kA Class SPD

The backup protection of an SPD is decided by two numbers: the maximum rating the SPD permits, and the prospective fault current at the board. Get the first from the SPD datasheet, the second from the installation, and select a device that satisfies both. A fuse chosen by habit usually satisfies neither, and the failure is silent until an SPD reaches end of life.

The 30kA impulse withstand is what separates this from a breaker of similar current rating. It means the device carries the surge that operates the SPD without itself opening, so protection is still connected after an event. That single property is the reason the accessory exists rather than being a marketing refinement.

LT-SSD50X SPD backup protector fuse-free disconnector four-pole 440VAC

Factory-Direct OEM / ODM Manufacturer

Tooling We Own, Standards We Follow

IEC 61643-11 platform · 250kA test station · OEM and ODM programmes

The modules on this page share a platform that has already passed type testing, so a variant order inherits that evidence instead of starting again. Manufacturing sits beside the laboratory, which is how we can verify a change before it enters a customer’s catalogue. Browse the rest of the range on AC SPD range.

  • Design control — drawings, BOM and test limits held under one quality system.
  • Lab access — impulse and residual-voltage checks run before a variant is released.
  • Branding — plate printing, laser marking and carton artwork prepared from your files.
  • Order size — sample lots, LCL and full containers all quoted from the same line.

LT-SSD50X SPD disconnector — SPD production hall with totes ready for assembly

Buying Guide

Select the disconnector from the SPD it protects and the fault level at the board. Both figures are needed.

  1. Read the maximum backup protection rating from the SPD datasheet you are installing.
  2. Obtain the prospective fault current at that board from the installation design.
  3. Choose the SSD rating that satisfies both, in this case the 30kA class for SPDs up to that withstand.
  4. Match the pole count to the SPD so the protector covers every protected path.
  5. Label the device clearly in the panel schedule so a future replacement is not substituted with an MCB.

Where the LT-SSD50X is the wrong choice

It is not a replacement for an MCB or a fused switch where the installation requires visible isolation, and it does not remove the need to calculate the prospective fault current — the disconnector has to be rated for it. Where a fuse is mandated by the local standard, this device cannot be substituted.

LT-SSD50X SPD disconnector — calibration bench with instruments at LEITAI

How We Support Your Business

LT-SSD50X SPD disconnector — automatic assembly equipment building SPD modules

OEM / ODM

Learn more →

Housing colour, pole count, voltage window, alarm contact and retail packaging built on our standard SPD platform — your logo on the front, your reference on the side.


Custom marking · Private label · Own artwork

LT-SSD50X SPD disconnector — operators assembling SPD modules on the LEITAI line

Wholesale

Learn more →

Factory-direct pricing with a per-item MOQ, mixing SPD models and backup protectors in one container for importers, panel builders and catalogue sellers.


Factory pricing · Mixed models · Container loading

LT-SSD50X SPD disconnector — electrical test bench used for SPD verification

Distributor Support

Learn more →

Account management, local voltage and standard advice, plus priority production slots for partners building an SPD range in their market.


Account manager · Market advice · Priority slots

Ready to Order the LT-SSD50X?

Tell us which SPD you are installing and the fault level at the board, and we will confirm whether the LT-SSD50X is the correct backup device or whether a higher rating is required.

Contact Our Sales Team

Frequently Asked Questions

What is an SPD backup fuse for?

It clears a sustained fault current through a failed SPD, which the upstream breaker may not detect. Without it, a faulted varistor can overheat or sustain an arc.

What does fuse-free mean?

The device trips on a sustained fault without a fuse element to replace, so it can be reset rather than re-fused. It also avoids fitting the wrong fuse rating.

Why is the tripping threshold 3A?

It is low enough to clear a fault current and high enough to ignore surge current, which is what prevents nuisance tripping after a lightning event.

Does it replace the need for a main breaker?

No. It sits immediately upstream of the SPD as its dedicated backup protection. The installation’s main protective devices remain as designed.

Which pole count should I choose?

Match it to the SPD. A 4P SPD takes a 4P disconnector so every protected path has backup protection.

Is it suitable for a TT system?

Yes, along with TN-S and TN-C. The device protects the SPD, and the earthing arrangement is handled by the SPD configuration.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “SPD Fuse 30kA Fuse-Free Disconnector — LT-SSD50X”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts