690V SPD for Wind Turbines — LT-T25/B+C 690V

LT-T25/B+C 690V — High Voltage Combined SPD for Renewable Systems

The 690V and 760V version of the combined Type 1+2 platform, built for wind turbine converters, box substations and mining supplies where the system voltage sits above ordinary low-voltage distribution. Same 25kA Iimp rating, with a 50kA short-circuit withstand.

Model

✓

LT-T25/B+C 690V SPD product photo

LT-T25/B+C 690V Combined Type 1+2 Surge ProtectorType 1+2 · Uc 690/760V · Iimp 25kA · Iscwr 50kA

Request a Wholesale Quotation

Type 1+2 combined · Uc 690/760V · MOQ quoted per configuration

Uc 690/760V
Iimp 25kA
Iscwr 50kA
Product Details
  • IEC class — Combined Type 1+2 to IEC 61643-11
  • Uc — 690 / 760 VAC
  • Iimp — 25 kA at 10/350 µs
  • In / Imax — 25 / 50 kA nominal, 50 / 120 kA maximum
  • Up — ≤2.0 kV
  • Short-circuit withstand — 50 kA
  • Application — wind converters, box substations, mining
Category:

The LT-T25/B+C 690V is a Type 1+2 combined surge protection device for supplies above ordinary low voltage: wind turbine nacelles, heavy plant and industrial systems running at 690V or 760V. It keeps the 25kA Iimp rating of the standard version and raises the maximum continuous voltage to suit the higher system voltage.

690V Surge Protection Device for Wind Turbines

Built for Supplies Above Ordinary LV

Wind turbine converters, box substations and mining distribution often operate at 690V or 760V, which is outside the window of a standard 275V or 440V device. This version carries the same combined Type 1+2 platform into that voltage range without asking the installer to stack devices in series.

A 50kA Short-Circuit Withstand

The fault levels in converter cabinets and mining supplies are higher than in commercial boards, which is why this version is rated at 50kA rather than the 25kA of the low-voltage unit. That figure decides whether the device survives an end-of-life failure intact.

Three-Pole by Application

690V converter supplies are typically three-wire, so the three-pole configuration is the standard build. Where a neutral is present, a four-pole arrangement can be supplied and we confirm it against the system drawing.

Vibration and Cycling in Mind

Turbine cabinets impose thermal cycling and vibration on everything inside them. The terminal arrangement and internal fixing of this version are specified with that in mind, which is why it is offered as a distinct product rather than a voltage variant of a general-purpose device.

Specifications

Series LT-T25/B+C 690V combined Type 1+2 surge protective device
IEC classification Type 1+2 combined, tested to IEC 61643-11
Maximum continuous voltage Uc 690 / 760 VAC
Impulse discharge current Iimp 25 kA (10/350 µs)
Nominal discharge current In 25 kA or 50 kA depending on version
Maximum discharge current Imax 50 kA or 120 kA depending on version
Voltage protection level Up ≤2.0 kV
Short-circuit withstand Iscwr 50 kA
Configurations 3P standard, 4P on request
Mounting 35mm DIN rail to EN 60715
Related models LT-T25/B+C 440V (low voltage version), LT-T15/B+C 690V (three-class)

Reading the LT-T25/B+C 690V specification

A 690V supply cannot use a 440V device, and the mistake is common enough that it is worth stating plainly: Uc must sit above the highest sustained voltage the system can produce, including regulation tolerance and the effects of regenerative operation. The 690/760V codes cover the two common wind and heavy-plant voltages.

The three-pole configuration is standard because the application is a three-phase supply without a distributed neutral. Vibration and thermal cycling matter more here than in a building board, which is why the terminal and housing design follows the same platform used in traction cabinets.

Wiring Diagram & Connection

The 690 V version is wired the same way as the 440 V unit but sits in a different system: the phase-to-phase voltage is 690 V and the neutral may be absent, so the diagram shows the three-phase connection without a neutral cartridge.

LT-T25 B+C 690V combined arrester wiring diagram for wind turbines
LT-T25/B+C 690 V connection in a wind turbine or heavy plant panel.

LT-T25/B+C 690V — Where the System Voltage Rules Out the Standard Device

A 690V converter supply is not simply a higher voltage version of a 400V board. The continuous voltage window, the fault level and often the physical arrangement all differ, and a device designed for 440V cannot simply be applied with a note on the drawing. This version exists because that gap is real and common in wind and mining work.

The 50kA short-circuit withstand is the detail that distinguishes it from the low-voltage version, and it reflects the fault levels found in converter cabinets. It is also the figure most often overlooked in specifications copied from a commercial building project, which is why we ask for the fault level rather than assuming it.

LT-T25 B plus C 690V Type 1+2 surge protector three-pole for wind turbine systems

Factory-Direct OEM / ODM Manufacturer

Your Specification, Our Production Line

Type-tested platform · private-label marking · batch test records

We quote from a real production schedule, not from a stock list, which is why a customer changing from a competitor’s module to ours usually keeps the same panel layout and only changes the label. Everything needed for that switch — drawings, curves and test sheets — is available before the order. The wider family is on AC SPD range.

  • Pre-order pack — datasheet, dimension drawing and declaration for your technical file.
  • Branding — printed fronts, side references and instruction sheets in your language.
  • Consistency — same platform across the range keeps panel stock simple for your customers.
  • Support — a named contact for repeat orders and technical questions.

LT-T25 B+C 690V SPD — SPD assembly hall with automated lines at LEITAI

Buying Guide

Confirm the system voltage and the fault level first; both differ from a standard commercial installation and both change the model.

  1. Confirm the nominal and maximum system voltage, distinguishing between 690V and 760V systems.
  2. Obtain the prospective fault current at the cabinet, since it determines whether the 50kA withstand is required.
  3. Confirm the pole arrangement from the system drawing, noting whether a neutral is distributed.
  4. Check the cabinet environment for temperature and vibration, and tell us if it is a turbine application.
  5. Confirm the backup protection rating for the higher fault level rather than reusing a low-voltage figure.

Where the LT-T25/B+C 690V is the wrong choice

It is not a substitute for a 440V device on an ordinary 400V board — the higher Uc raises the clamping level and gives away protection margin for no benefit. Where the system is a standard three-phase four-wire supply, the standard LT-T25/B+C is the correct choice.

LT-T25 B+C 690V SPD — instrument bench for SPD calibration and testing

How We Support Your Business

LT-T25 B+C 690V SPD — soldering cells used in surge protector production

OEM / ODM

Learn more →

We print your brand on the module front and pack to your carton design; ODM covers new pole layouts, alternative voltage windows and signalling options.


Tooling in house · Branded packing · ODM design

LT-T25 B+C 690V SPD — module assembly zone with operators at LEITAI

Wholesale

Learn more →

Volume pricing on the whole LT range, with sample lots for tender packages and full containers for stock orders.


Bulk pricing · Samples · Firm lead times

LT-T25 B+C 690V SPD — SPD routine test bench at the LEITAI laboratory

Distributor Support

Learn more →

Technical files, selection curves and local standard guidance so your sales team can specify the right type on the first visit.


Datasheets · Selection help · Training

Ready to Order the LT-T25/B+C 690V?

Send the converter or box substation drawing with the system voltage and fault level, and we will confirm the 690V or 760V code and the pole arrangement for the cabinet.

Contact Our Sales Team

Frequently Asked Questions

What is a 690V SPD used for?

It protects equipment on supplies above ordinary low voltage: wind turbine systems, heavy plant and industrial installations running at 690V or 760V. The higher Uc rating is what makes it suitable there.

Can a 440V SPD be used on a 690V system?

No. The maximum continuous voltage must exceed the highest sustained system voltage; a 440V device on a 690V supply would be operating beyond its rating.

Why is it three-pole?

The application is a three-phase supply without a distributed neutral, so the three phase paths plus the earth reference are what needs protecting. Four-pole versions are available on request.

Is it suitable for a wind turbine nacelle?

Yes, and the construction takes account of the thermal cycling and vibration found in that environment. Tell us the application at quotation stage so the documentation matches.

Does it come in a four-pole version?

A four-pole arrangement can be supplied where a neutral is distributed. Most 690V converter supplies are three-wire, so the three-pole version is standard.

What protection level does it give?

Up to 2.0kV. That is a first-stage figure, and sensitive control electronics downstream still benefit from a second-stage device.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “690V SPD for Wind Turbines — LT-T25/B+C 690V”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts