The LT-X50 is a Type 1 surge protection device rated 50kA Iimp (10/350 µs) for structures that cannot avoid exposure — towers, hilltop sites, coastal installations and buildings with a large number of down conductors. It shares the housing and the graphite gap technology of the smaller ratings, but the stack carries the highest charge of the range at a clamping level of ≤2.5kV.
Type 1 Surge Protection Device 50kA: Key Features
For Sites That Cannot Avoid Exposure
Telecom shelters, water towers, remote pumping stations and masts share a characteristic: the structure is the highest object locally and the supply is often overhead. Under those conditions the share of lightning current reaching the electrical installation is at the top of the scale, and fifty kiloamps of 10/350 is the rating that covers it.
Charge Capacity, Not Just Peak
The difference between 30kA and 50kA in a gap device is mostly plate area, which determines how much charge the gap can transfer before erosion becomes significant. For a site that sees several events a season, that difference sets the service interval rather than the protection level.
Consistent With the Smaller Ratings
The terminal layout, the rail mounting and the status indication follow the same pattern as the LT-X15 and LT-X30, so a specification that mixes ratings across a site still uses one installation method and one set of drawings.
Sized Together With the Earth Termination
A high-current entry arrester only performs if the earthing resistance and the bonding conductors can carry the current away. Where the measured earth resistance is high, improving the electrode is a more effective investment than moving to a larger device.
Specifications
| Series | LT-X50 Type 1 voltage switching SPD |
|---|---|
| IEC classification | Type 1 / Class I, tested to IEC 61643-11 |
| Maximum continuous voltage Uc | 275 / 320 / 385 / 440 VAC |
| Impulse discharge current Iimp | 50 kA (10/350 µs) |
| Voltage protection level Up | ≤2.5 kV |
| Protective element | graphite spark gap, maximum plate stack |
| Follow current | none — self-extinguishing |
| Configurations | 3P+NPE standard, other layouts on request |
| Mounting | 35mm DIN rail to EN 60715 |
| Site conditions | tall or isolated structures, overhead supply |
| Related models | LT-X15 (15kA), LT-X30 (30kA), LT-T25 (hybrid with MOV) |
Reading the LT-X50 specification
At this rating the limiting factor is usually charge rather than peak current. A 10/350 µs waveform delivers a long tail, and the gap has to absorb that energy without welding shut or failing to extinguish. Fifty kiloamps per pole is the top of the LT gap range, and it is specified where the risk assessment returns a partial lightning current that the 30kA unit cannot cover.
Because the device is physically the same as the LT-X15 and LT-X30, the panel layout does not change when a project moves up the range. The earth conductor sizing and the equipotential bonding do change, and those are set by the installation standard rather than by the SPD.
Wiring Diagram & Connection
The LT-X50 is the largest gap in the range and belongs at the service entrance of an exposed structure. Its discharge path carries 50 kA per pole, so both the phase tails and the earth return are sized by the lightning current, not by the load.

LT-X50 — Designed for the Building That Attracts Lightning
There is a category of installation where lightning is not a statistical risk but an expected annual event. A mast, a tower, a hilltop pump station: the structure is the local high point, the supply run is long and often overhead, and the entry protection is doing work every season. In that situation the entry device is a consumable, and its charge capacity determines how often it is a consumable.
Fifty kiloamps of 10/350 is the top of the gap range for that reason. It does not lower the protection level compared with smaller versions — the clamping voltage is essentially the same — but it survives more and larger events before the electrodes need attention. Where the site is exposed but the earth termination is poor, correcting the earthing comes first, because no arrester can discharge into an electrode that will not take the current.

Factory-Direct OEM / ODM Manufacturer
From Mould to Carton, Under One Roof
Liushi, Zhejiang · fully automatic SPD line · OEM, ODM and wholesale
Choices that normally need a tooling investment — a different housing colour, an extra pole, a longer terminal shroud — are routine here because the machine shop, the moulding area and the assembly line are on the same site. That is the practical difference between buying from the plant and buying from a catalogue. See Type 1 SPD range for the models this platform covers.
- In-house moulds — new cavities cut and proven without an outside toolmaker.
- Assembly — semi-automatic cells keep torque and fit consistent across a batch.
- Quality gate — incoming varistors are graded before they reach the assembly line.
- Export packing — cartons, labels and pallet marks prepared to the destination market.

Buying Guide
- Take the Iimp requirement from the risk assessment for the actual structure, not from a generic specification.
- Check the measured earth resistance and the bonding conductor sizes before ordering a larger arrester.
- Confirm the supply entry route; overhead and unshielded routes carry more current into the installation.
- Allow rail space and cable clearance for a 3P+NPE assembly with short, direct leads to the earth bar.
- Arrange an inspection routine after the lightning season, since the device is expected to operate.
Where the LT-X50 is the wrong choice
This is not a default choice for exposed buildings. Where the assessment returns 15kA or 30kA, the smaller ratings in the same housing do the job at lower cost and with the same clamping level. The LT-X50 also does not replace the Type 2 stage: 2.5kV is a first-stage residual voltage, and a sub-board still needs a 40kA Type 2 device to bring the level down for equipment.
How We Support Your Business
OEM / ODM
Private-label programmes run on the same type-tested platform, so a rebranded unit keeps the ratings, curves and approvals of the original.
Type-tested base · Rebranding · Carton design
Wholesale
Container planning, mixed pallets and consistent batch quality for wholesalers supplying panel builders and contractors.
Container plan · Mixed pallets · Batch records
Distributor Support
Priority production slots and a named account contact for partners promoting the range at trade shows and in tender work.
Priority slots · Named contact · Tender files
Ready to Order the LT-X50?
For exposed sites, send the risk assessment, the earth resistance measurement and the supply arrangement, and we will confirm whether the LT-X50 is required or whether earthing improvements would serve you better.
Frequently Asked Questions
What is a 50kA Type 1 SPD used for?
It is used where the calculated partial lightning current at the service entrance is high: tall or isolated structures, sites with many down conductors, and installations where the supply arrives overhead and exposed.
Is 50kA Iimp the same as 50kA Imax?
No. Iimp is tested with a 10/350 µs lightning waveform and describes charge capacity; Imax is tested with 8/20 µs and describes a single induced surge. A Type 2 device rated 50kA Imax is not equivalent to this unit.
Can it be installed without an external lightning protection system?
It can, but it is rarely the right specification. Without an LPS the current reaching the conductors is normally handled by a Type 2 device, and the higher clamping level of a gap arrester is a disadvantage rather than a benefit.
Can I install it without a lightning protection system?
A Type 1 device is normally specified with a lightning protection system, since it exists to handle partial lightning current. Without an LPS, a Type 2 device at the origin is usually the correct specification.
Is an external disconnector required?
Not for follow current, because there is none. Where local practice requires a disconnector ahead of an SPD, an LT-SSD unit can be installed, rated for the installation’s fault level.
What earthing does it need?
A low-resistance earth termination bonded to the main earthing terminal, with the arrester connected by the shortest practical route. The device protects nothing if the earth path cannot carry the discharge.