Surge Arrester Type 1 25kA for Direct Strikes — LT-T25

LT-T25 — Pure Type 1 SPD with TOV 1200V

A Type 1 device with no Type 2 claim: 25kA of 10/350 lightning current, a 1200V temporary overvoltage withstand, a 50kA short-circuit withstand and a remote contact as standard. For entrances where the Type 2 duty is handled by a separate device further downstream.

Model

✓

LT-T25 SPD product photo

LT-T25 Pure Type 1 Surge ProtectorType 1 (T1) · Iimp 25kA · TOV 1200V · Iscwr 50kA

Request a Wholesale Quotation

Type 1 (Class I) · Iimp 25kA · MOQ quoted per configuration

Iimp 25kA
TOV 1200V
Iscwr 50kA
Product Details
  • IEC class — Type 1 (Class I) to IEC 61643-11
  • Uc — 275 / 320 / 385 / 440 VAC
  • Iimp — 25 kA at 10/350 µs
  • Up — 1.4 / 1.6 / 1.8 / 2.0 kV (L-N)
  • Temporary overvoltage — 1200V withstand
  • Short-circuit withstand — 50 kA
  • Signalling — remote contact standard
Categories: ,

The LT-T25 is a pure Type 1 surge arrester rated 25kA Iimp (10/350 µs), built for direct-strike protection without any Type 2 claim. Unlike the gap models it uses a hybrid element, so the residual voltage is lower at 1.4kV on the 275V code — useful where the entry device also has to reduce the let-through level rather than only discharge current.

Surge Arrester Type 1 25kA for Direct Strikes

A Type 1 Device Without a Type 2 Claim

Devices that carry both ratings are convenient but their Type 1 performance is a compromise. This unit does one job: it handles the partial lightning current at the entrance, and it does so with a 25kA rating, a 1200V temporary overvoltage withstand and a 50kA short-circuit withstand that a combined device cannot match at the same size.

Built to Ride Through Abnormal Supply

The 1200V TOV withstand is the specification that keeps the device in service during a lost neutral or a transformer fault. Those events last long enough to destroy a device that cannot tolerate them, and they are more common than lightning in many networks.

Designed for a Staged Design

Because the Type 2 duty is delegated, the design is explicit about where each function sits: this device at the entrance, a lower-clamping Type 2 device at the sub-main, and optionally a Type 3 device at the equipment. That structure is easier to calculate and easier to defend in a design review than a single combined unit.

Fifty kA of Fault Withstand

At the entrance, fault levels are at their highest. A 50kA withstand means the device survives an end-of-life short circuit long enough for the incoming protection to operate, which is the scenario that actually destroys panels.

Specifications

Series LT-T25 pure Type 1 surge protective device
IEC classification Type 1 / Class I, tested to IEC 61643-11
Maximum continuous voltage Uc 275 / 320 / 385 / 440 VAC
Impulse discharge current Iimp 25 kA (10/350 µs)
Voltage protection level Up 1.4 / 1.6 / 1.8 / 2.0 kV by code
Temporary overvoltage TOV 1200V withstand
Short-circuit withstand Iscwr 50 kA
Configurations 1P, 1P+NPE, 2P, 3P, 3P+NPE, 4P
Signalling remote contact standard
Related models LT-T25/B+C (combined Type 1+2), LT-X50 (gap type, 50kA)

Reading the LT-T25 specification

The distinction from the X range is the element. A graphite gap has no leakage and no follow current but clamps high; a hybrid stack brings Up down to 1.4kV on the 275V code, which shortens the gap that the downstream Type 2 device has to close. The 25kA Iimp rating places it between the LT-X15 and the LT-X30 in charge capacity.

It is a Type 1 device only. That matters at specification stage: a schedule that asks for Type 1+2 in one unit should use the LT-T25/B+C instead, while a staged design with a separate Type 2 device downstream is what this model is built for.

Wiring Diagram & Connection

The LT-T25 is a pure Type 1 voltage-switching device: no In or Imax figure applies, so the wiring only has to carry the lightning impulse and the follow current that the gap quenches. Terminals and signal contact are shown at the right of the diagram.

LT-T25 pure Type 1 voltage switching SPD wiring diagram with signal contact
LT-T25 connection as a voltage-switching Type 1 device at the incomer.

LT-T25 — One Duty, Done Properly

There is a design philosophy argument buried in the choice between this device and the combined version beside it. A combined unit is compact and hard to misapply; a dedicated unit is more capable at its own job and makes the staging of the design explicit. Neither is wrong, and the selection usually follows the competence of whoever will install and inspect the panel.

The figures that justify the dedicated device are the withstand values. Twenty-five kiloamps of 10/350 lightning current, 1200V of temporary overvoltage tolerance and 50kA of short-circuit withstand, all in one body, are the marks of an entrance device built for an entrance rather than for a catalogue page that needs to cover two categories at once.

LT-T25 pure Type 1 surge protector four-pole 25kA Iimp for service entrances

Factory-Direct OEM / ODM Manufacturer

We Manufacture, You Brand

Module moulding in house · MOV selection and thermal parts · OEM branding

Every LT component on this page — housing, busbar, varistor stack and thermal disconnector — is produced and assembled at our own plant in Liushi, Zhejiang, which is why a special voltage, pole count or marking requirement costs you a production slot rather than a new supplier qualification. The full AC range sits on our Type 1 SPD range page.

  • OEM branding — logo, model number and rating text printed on the module front and the carton.
  • ODM options — housing colour, pole count, voltage window, remote-signal contact and retail packing.
  • Testing — residual voltage and thermal trip checked on every unit, records kept per batch.
  • MOQ — quoted per configuration — mixed models can share one container.

LT-T25 Type 1 SPD — automated production line at the LEITAI factory

Buying Guide

Choose this device when the Type 2 function is handled elsewhere. Confirm that separation before ordering.

  1. Confirm the required Iimp from the risk assessment and check the 25kA rating covers it.
  2. Establish where the Type 2 stage will sit and confirm the cable length between the two devices.
  3. Select the voltage code, noting that the protection level rises from 1.4kV at 275V to 2.0kV at 440V.
  4. Confirm the fault level at the entrance against the 50kA withstand.
  5. Wire the remote contact into the monitoring system and record the device in the maintenance schedule.

Where the LT-T25 is the wrong choice

Do not use it as the only device in an installation. Its Type 1 rating covers the entry position, and the residual voltage still has to be reduced by a Type 2 stage before equipment. Where the risk assessment calls for a gap rather than a hybrid — typically where follow current must be avoided entirely — the LT-X30 is the correct choice.

LT-T25 Type 1 SPD — SPD routine test bench at the LEITAI laboratory

How We Support Your Business

LT-T25 Type 1 SPD — dual soldering machines on the LEITAI production line

OEM / ODM

Learn more →

We print your brand on the module front and pack to your carton design; ODM covers new pole layouts, alternative voltage windows and signalling options.


Tooling in house · Branded packing · ODM design

LT-T25 Type 1 SPD — operators assembling SPD modules on the LEITAI line

Wholesale

Learn more →

Volume pricing on the whole LT range, with sample lots for tender packages and full containers for stock orders.


Bulk pricing · Samples · Firm lead times

LT-T25 Type 1 SPD — type test certificates and honours on show at LEITAI

Distributor Support

Learn more →

Technical files, selection curves and local standard guidance so your sales team can specify the right type on the first visit.


Datasheets · Selection help · Training

Ready to Order the LT-T25?

If your design separates the Type 1 and Type 2 duties, send us the entrance details and the position of the second stage, and we will confirm the LT-T25 code and the co-ordination.

Contact Our Sales Team

Frequently Asked Questions

What does pure Type 1 mean?

It means the device is tested and rated only for the 10/350 µs lightning waveform, with no Type 2 (8/20 µs) rating claimed. It is intended as the first stage, with a Type 2 device downstream.

Is a hybrid Type 1 better than a spark gap?

It depends on the position. A hybrid clamps lower, which helps the downstream stage; a gap has no leakage and no follow current, which suits entries where those properties matter. Neither is universally better.

What is the difference between 25kA and 30kA Iimp?

Both are Type 1 ratings; the difference is charge capacity per pole. The right figure comes from the risk assessment, and the two models share the same panel footprint, so changing rating does not change the layout.

Why is the short-circuit withstand important?

If the element fails, it fails as a short circuit. The device must contain that fault until the backup protection clears it, and 50kA covers the fault levels found at service entrances.

Is the remote contact optional?

It is fitted as standard. At an entrance device that is often out of sight, the signal is the difference between knowing and assuming.

Which codes are available?

275, 320, 385 and 440V, with protection levels from 1.4kV to 2.0kV. The code is chosen from the system voltage and the equipment withstand.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “Surge Arrester Type 1 25kA for Direct Strikes — LT-T25”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts