The LT-SSD80 is an 80kA SPD backup fuse for 60kA to 80kA arresters, the middle size in the SSD range and the one matched to the 60 and 80kA Type 2 devices. It provides the series disconnection that a large Type 2 device needs, without the fuse selection problem that comes with matching a conventional element to an 80kA arrester.
80kA SPD Backup Fuse for 60-80kA Arresters
Matched to the Bigger Arresters
A backup device for an 80kA arrester has to pass more surge energy than one for a 30kA device, and using the smaller accessory in front of a larger SPD is a mismatch that shows up as a device opening during an event it should have ridden through. This version is rated for the duty.
Eighty kA Without Tripping
The withstand figure is the property that makes the accessory work: the SPD conducts, the backup device does not open, and protection remains in circuit for the next event. After a surge is when protection matters most, so a device that disconnects itself is worse than no device at all.
For Floor and Sub-Main Boards
This class is used where the SPD is a 60kA or 80kA device, which places it at distribution and sub-main level rather than at the origin. The pole count and the 440V rating cover the usual configurations at that level.
Consistent With the Range
The body, terminals and rail mounting follow the same pattern as the smaller and larger members of the SSD family, so a project specifying several boards uses one accessory type per rating with a common installation method.
Specifications
| Series | LT-SSD SPD backup protection range |
|---|---|
| Function | dedicated short-circuit and backup protection for SPDs |
| Rated voltage Ue | 440 VAC |
| Impulse withstand Imax | 80 kA (8/20 µs) without tripping |
| Tripping current It | 3 A |
| Configurations | 1P, 2P, 3P, 4P |
| Matched SPD class | 60kA to 80kA maximum discharge current |
| Mounting | 35mm DIN rail to EN 60715 |
| Positioning | immediately upstream of the SPD |
| Related models | LT-SSD50X (30kA class), LT-SSD160 (160kA class) |
Reading the LT-SSD80 specification
The matching rule is simple and often ignored: the backup device’s impulse withstand must be at least the arrester’s rating. Pairing an 80kA SPD with a backup rated for 40kA leaves the weak point in the chain, and the failure mode is a backup device that opens during a surge instead of after a fault.
The switch is available in 1P to 4P and mounts on the same rail as the arrester it protects. Tripping is on sustained fault current rather than on surge, so a lightning event does not take the protection out of service.
Wiring Diagram & Connection
The 80 kA version is chosen by the Imax of the arrester behind it, so an LT-80 or LT-40 bank takes one LT-SSD80 per pole. Wiring stays the same as for the smaller unit; only the let-through behaviour under a surge changes.

LT-SSD80 — Choosing the Backup Device From the SPD, Not the Load
The common mistake in specifying backup protection is to size it from the load current. The correct basis is the SPD’s maximum permitted backup rating and the prospective fault current at the board, and neither of those relates to how much current the building draws. A 100A supply can need a 3A backup device in front of its arrester.
The second mistake is to use the same accessory across a project regardless of the SPD rating. That works until a large surge arrives at a board where an undersized device opens and the installation loses protection silently. Matching the accessory class to the arrester class is what keeps the scheme intact under real conditions.

Factory-Direct OEM / ODM Manufacturer
Built Here, Labelled for You
Injection moulding · varistor grading · 100% routine test · private label
Because the mould, the varistor grading bench and the impulse generator all belong to the same company, a private-label run does not depend on a third party agreeing to change a tool. Tell us the model designation you sell under and we print, pack and test to that name. More configurations are listed under AC SPD range.
- Private label — your brand on the front, your reference on the side, your language in the manual.
- Custom build — voltage window, pole layout, alarm contact and packaging format are open to change.
- Traceability — each carton carries the batch number that links back to its test record.
- Lead time — confirmed against the actual production schedule when the order is placed.

Buying Guide
- Identify the maximum discharge current of the SPD installed at that board.
- Read its permitted maximum backup protection from the datasheet.
- Confirm the prospective fault current at the board.
- Select the SSD class that carries the surge without tripping and clears a failed element at that fault level.
- Match the pole count to the SPD and label the device in the panel schedule.
Where the LT-SSD80 is the wrong choice
It is not the right size for a 40kA arrester — the LT-SSD50X covers that class. Nor is it a substitute for the main protective device: it protects the SPD, not the installation.
How We Support Your Business
OEM / ODM
Send a drawing and we return a sample: pole count, voltage window, terminal style, marking and packaging are all open to change.
Sample first · Drawing to part · Own marking
Wholesale
Tiered pricing across the SPD range with flexible quantities per model, so a wholesaler can test a market before committing to a container.
Tiered pricing · Flexible qty · Test orders
Distributor Support
Application advice for local earthing systems, plus the test evidence needed to satisfy inspectors and consultants.
Application help · Test evidence · Inspections
Ready to Order the LT-SSD80?
Tell us the SPD model and the fault level at each board, and we will confirm the correct SSD class for each one rather than applying a single rating across the project.
Frequently Asked Questions
Which backup device matches an 80kA SPD?
One rated at least 80kA impulse withstand, which is what this unit provides. Undersizing it moves the failure point into the backup device.
Can I use a standard fuse instead?
Where the local standard permits it and the coordination is calculated, yes. The advantage of this unit is that the rating is matched and the tripping characteristic ignores surge current.
Does it trip on every surge?
No. It trips on sustained fault current, not on the short surge current that passes during a lightning event.
What is the tripping current for?
3A allows a failed SPD element to be cleared without the device reacting to normal leakage or a modest surge.
Is it DC rated?
No, it is an AC accessory rated 440V. PV applications require DC-rated isolation and protection.
Can it be used on a single-phase board?
Yes, in the single or two-pole configuration. The class is chosen from the SPD, not the phase count.