DC SPD 1000V Type 2 for Combiner Boxes — LT-40/G1000

LT-40/G1000 — 1000V PV Type 2 SPD with Signalling

A Type 2 photovoltaic surge protector for 1000V DC systems, in both U and Y configurations, with 500A of PV current capability and a remote signalling option. The workhorse device for commercial rooftop and small ground-mount combiners.

Model

✓

LT-40/G1000 SPD product photo

LT-40/G1000 PV Type 2 Surge ProtectorPV Type 2 · Ucpv 1000V DC · In 20kA · Up 3.5kV

Request a Wholesale Quotation

Type 2 (PV, IEC 61643-31) · Ucpv 1000V · MOQ quoted per configuration

Ucpv 1000V
Iscpv 500A
Remote signal option
Product Details
  • Standard — IEC 61643-31 / EN 50539-11
  • Ucpv — 1000 VDC
  • In / Imax — 20 kA / 40 kA at 8/20 µs
  • Up — ≤3.5 kV
  • Configurations — U type 2P (DC+/DC-) and Y type 3P (DC+/PE/DC-)
  • PV short-circuit current — Iscpv 500A
  • Options — remote signalling version available
Category:

The LT-40/G1000 is a 1000V DC Type 2 SPD for PV combiner boxes and the inverter DC side, rated In 20kA and Imax 40kA with Up ≤3.5kV. It is built to IEC 61643-31 and EN 50539-11, the standards that govern DC-side protection rather than the AC 61643-11 used for board-mounted devices. Both U (2-pole) and Y (3-pole) configurations are available, with an optional remote signalling contact that reports a failed cartridge back to the monitoring system.

1000V DC SPD for Combiner Boxes: Key Features

The Common Commercial Array Voltage

A thousand volts DC is the standard for commercial rooftop and small ground-mount systems, and it is where the largest number of installations sit. This device is the Type 2 member of that family: it protects strings and combiners without the Type 1 claim that an exposed array would need.

Two Wiring Configurations in One Platform

U type covers the positive and negative conductors in a 2P body; Y type adds the earth path in a 3P body. Because both share the same element and terminals, a designer can choose on the earthing arrangement rather than on product availability.

Five Hundred Amps of String Current

The Iscpv rating of 500A is what allows the device to sit in a combiner handling several parallel strings. Undersizing this figure produces a device that runs warm, and the correction is a larger rating rather than a different product.

Signalling for Distributed Arrays

The signalling version reports a failed cartridge to the monitoring system. On a large rooftop array with dozens of combiners, a visual inspection is impractical and the signal is the only practical way to keep protection in service.

Specifications

Series LT-40/G1000 PV Type 2 surge protective device
Standard IEC 61643-31, EN 50539-11
Maximum continuous voltage Ucpv 1000 VDC
Nominal discharge current In 20 kA (8/20 µs)
Maximum discharge current Imax 40 kA (8/20 µs)
Voltage protection level Up ≤3.5 kV
Configurations U type 2P and Y type 3P
PV short-circuit current Iscpv 500 A
Options remote signalling version
Mounting 35mm DIN rail in a combiner or inverter enclosure
Related models LT-40/G600 (600V), LT-40/G1500 and G2000 (higher voltages), LT-15T/G1000 (Type 1+2)

Reading the LT-40/G1000 specification

U and Y are chosen from the array earthing arrangement, not from preference. U protects across DC positive and negative in a 2P body and suits an ungrounded array; Y adds a third pole to the protective earth and is used where the array has a functional earth. The choice changes the enclosure space and the earth bar layout, so it has to be fixed before the combiner box is ordered.

Two ratings look unusual next to an AC device and both are correct. Iscpv 500A is the maximum string fault current the device can carry, which is what allows one unit to sit in a combiner fed by several parallel strings — understate it and the device runs warm. Up ≤3.5kV is high by AC standards because the system voltage is 1000V DC; the protection level scales with the voltage class, so a direct comparison with a 1.4kV AC device is not meaningful.

Wiring Diagram & Connection

The 1000 V member of the G family is the one most often fitted at the inverter DC side. The diagram shows the two wiring options and the signal terminals that report a failed cartridge back to the monitoring system.

LT-40/G1000 1000V DC combiner box SPD wiring diagram with remote signal

LT-40/G1000 wiring in a string combiner, U or Y configuration.

LT-40/G1000 — The Type 2 Workhorse for Commercial Arrays

Not every array needs a Type 1 device. Where the mounting structure is shielded by taller buildings, or the array is small and low, the risk of partial lightning current reaching the DC conductors is limited, and a Type 2 device at the combiner is the proportionate specification. That is the majority of commercial rooftop work, which is why this rating carries the volume.

The practical question buyers ask is where to put it. The combiner box is usually the answer: several strings meet there, one device covers the group, and the run to the inverter starts at that point. Putting a device at each string end costs more and protects less, because it does not address the cable between the combiner and the inverter.

LT-40 G1000 photovoltaic Type 2 surge protector 1000V DC Y configuration

Factory-Direct OEM / ODM Manufacturer

From Mould to Carton, Under One Roof

Liushi, Zhejiang · fully automatic SPD line · OEM, ODM and wholesale

Choices that normally need a tooling investment — a different housing colour, an extra pole, a longer terminal shroud — are routine here because the machine shop, the moulding area and the assembly line are on the same site. That is the practical difference between buying from the plant and buying from a catalogue. See DC SPD range for the models this platform covers.

  • In-house moulds — new cavities cut and proven without an outside toolmaker.
  • Assembly — semi-automatic cells keep torque and fit consistent across a batch.
  • Quality gate — incoming varistors are graded before they reach the assembly line.
  • Export packing — cartons, labels and pallet marks prepared to the destination market.

LT-40/G1000 PV SPD — automatic SPD production line running at LEITAI

Buying Guide

Confirm the array voltage class and the installation point first; both decide the configuration.

  1. Confirm the array’s maximum voltage at the coldest expected temperature, not only the nominal string voltage.
  2. Check the combiner fault current against the 500A Iscpv rating, allowing for module tolerance.
  3. Choose U or Y configuration from the array earthing arrangement.
  4. Decide whether the signalling version is needed, based on how often the combiner will be accessed.
  5. Confirm the DC isolation arrangement and that all devices on that side are DC rated.

Where the LT-40/G1000 is the wrong choice

An exposed ground mount, an elevated structure or any array that forms part of a lightning protection system needs a Type 1 device, not this one — the LT-15T/G1000 carries the 10/350 Iimp rating for that position. A 1500V array cannot use this device at all; the LT-40/G1500 is the correct voltage class. And where the combiner fault current exceeds 500A, the Iscpv rating is the limiting figure and a larger device is required — the voltage rating alone does not decide it.

LT-40/G1000 PV SPD — manual module assembly zone at the Lei tai factory

How We Support Your Business

LT-40/G1000 PV SPD — component feeding and assembly equipment at LEITAI

OEM / ODM

Learn more →

Private-label programmes run on the same type-tested platform, so a rebranded unit keeps the ratings, curves and approvals of the original.


Type-tested base · Rebranding · Carton design

LT-40/G1000 PV SPD — soldering station on the LEITAI production floor

Wholesale

Learn more →

Container planning, mixed pallets and consistent batch quality for wholesalers supplying panel builders and contractors.


Container plan · Mixed pallets · Batch records

LT-40/G1000 PV SPD — instrument bench for SPD calibration and testing

Distributor Support

Learn more →

Priority production slots and a named account contact for partners promoting the range at trade shows and in tender work.


Priority slots · Named contact · Tender files

Ready to Order the LT-40/G1000?

Send the array layout, the string voltage and the combiner current, and we will confirm the configuration and whether the Type 1+2 device is needed instead.

Contact Our Sales Team

Frequently Asked Questions

What is a DC SPD used for?

A DC SPD limits surge voltage on the direct-current side of a PV array, between the strings and the inverter. It is a separate device from an AC SPD because DC arc behaviour and the applicable standard differ — DC units are tested to IEC 61643-31 rather than 61643-11.

What is the difference between U and Y configuration?

U type protects across DC positive and negative in a 2P body. Y type adds the protective earth path in a 3P body and is used where the array has a functional earth. Ungrounded arrays normally take U.

Does a PV SPD need a backup fuse?

Yes, and it matters more on the DC side than on AC: a faulted varistor can sustain an arc that the inverter cannot interrupt. The fuse must be rated for the array’s Iscpv and for DC voltage, and the combiner’s own string fuses do not automatically cover this.

When do I need Type 1+2 instead of Type 2?

When the array structure is part of, or effectively acts as, a lightning protection system: exposed roofs, open ground mounts and elevated structures. Shielded urban rooftops normally suit the Type 2 device.

Can the signalling version be retrofitted?

The signalling variant is ordered as a distinct model. Where monitoring is expected later, order the version with signalling at the start rather than replacing devices on the roof.

Does the device need a special base?

No, it mounts on standard 35mm DIN rail like the AC range, which is why it fits the same combiner enclosures.

Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “DC SPD 1000V Type 2 for Combiner Boxes — LT-40/G1000”

Your email address will not be published. Required fields are marked *

Contact Us

Zhejiang Leitai Electrical Co., Ltd., a Chinese high-tech enterprise, focuses on R&D, production and sales of lightning protection products.

Tel: 0577-62625686

Mobile: 133 5337 7303

WhatsApp: +86 137 3677 5008

E-mail: leitai@leitai.cn

Address: No. 17, Zhenmin Road, Sibaiqiao Industrial Zone, Liushi Town, Wenxiang City, Zhejiang Province

Follow Us

Official Accounts